Offshorecable summary - Power Cables High Voltage - 3,6 to 30kV.

Hopefully this list will be usefully in you daily search after resources within the Offshore / Marina /Ex / Hazardous field.

 

Power cable high voltage - Flame retardant RFOU 

RFOU 3,6/6 (7,2) kV P2/ P9

  • Power Cable Fixed Installation.
  • Conductor: Tinned stranded and compressed copper (STCC), IEC 60228 Class2
  • Conductor screen semiconductive: Semiconductive layer (EP-rubber)
  • Insulation: (R) EP-rubber, IEC 60092-360 (EPR)
  • Insulation screen semiconductive: Semiconductive layer (EP-rubber)
  • Lay up / Shielding: Cores are laid up together. Cores are identified by Brown, Black or Grey threads under and over the metallic screen on each conductor.
  • Inner covering: (F) Flame retardant and halogen-free thermoset compound.
  • Tape over inner covering: PET tape
  • Armour / screen: (O) Tinned annealed copper wire braid
  • Tape over armour / screen: PET tape
  • Outer sheath: (U) Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-360)
  • Outer sheath colour: Red

Application/ Use:

  • Fixed installation for medium voltage (MV) power in both EX- and safe areas, general purposes.
  • For installation in areas exposed to MUD and drilling/ cleaning fluids.

RFOU 3.6 67.2kV P2 P9

RFOU 6/10 (12) kV P3/ P10

  • Power Cable Fixed Installation.
  • Conductor: Tinned stranded and compressed copper (STCC), IEC 60228 Class2
  • Conductor screen semiconductive: Semiconductive layer (EP-rubber)
  • Insulation: (R) EP-rubber, IEC 60092-360 (EPR)
  • Insulation screen semiconductive: Semiconductive layer (EP-rubber)
  • Lay up / Shielding: Cores are laid up together. Cores are identified by Brown, Black or Grey threads under and over the metallic screen on each conductor.
  • Inner covering: (F) Flame retardant and halogen-free thermoset compound.
  • Tape over inner covering: PET tape
  • Armour / screen: (O) Tinned annealed copper wire braid
  • Tape over armour / screen: PET-tape
  • Outer sheath: (U) Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-360)
  • Outer sheath colour: Red

Application/ Use:

  • Fixed installation for medium voltage (MV) power in both EX- and safe areas, general purposes.
  • For installation in areas exposed to MUD and drilling / cleaning fluids.
  • Meets the MUD resistance requirement in NEK TS 606:2009

RFOU 3.6 67.2kV P2 P9

RFOU 8,7/15 (17,5) kV P4/ P11

  • Power Cable Fixed Installation.
  • Conductor: Tinned stranded and compressed copper (STCC), IEC 60228 Class2
  • Conductor screen semiconductive: Semiconductive layer (EP-rubber)
  • Insulation: (R) EP-rubber, IEC 60092-360 (EPR)
  • Insulation screen semiconductive: Semiconductive layer (EP-rubber)
  • Lay up / Shielding: Cores are laid up together. Cores are identified by Brown, Black or Grey threads under and over the metallic screen on each conductor.
  • Inner covering: (F) Flame retardant and halogen-free thermoset compound
  • Tape over inner covering: PET-tap
  • Armour / screen: (O) Tinned annealed copper wire braid
  • Tape over armour / screen: PET-tape
  • Outer sheath: (U) Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 6009-360)
  • Outer sheath colour: Red

Application/ Use:

  • Fixed installation for medium voltage (MV) power in both EX- and safe areas, general purposes.
  • For installation in areas exposed to MUD and drilling / cleaning fluids.
  • Meets the MUD resistance requirement in NEK TS 606:2009

RFOU 8.7 1517.5kV P4 P11

RFOU 12/20 (24) kV P19/ P21

  • Power Cable Fixed Installation.
  • Conductor: Tinned stranded and compressed copper (STCC), IEC 60228 Class2
  • Conductor screen semiconductive: Semiconductive layer (EP-rubber)
  • Insulation: (R) EP-rubber, IEC 60092-360 (EPR)
  • Insulation screen semiconductive: Semiconductive layer (EP-rubber9
  • Lay up / Shielding: Cores are laid ut together. Cores are identified by Brown, Black or Grey threads under and over the metallic screen on each conductor.
  • Inner covering: (F) Flame retardant and halogen-free thermoset compound
  • Tape over inner covering: PET-tape
  • Armour / screen: (O) Tinned annealed copper wire braid
  • Tape over armour / screen: PET-tape
  • Outer sheath: (U) Flame retardant, halogen-free and mud resistant thermoseth compound, SHF2 (IEC 60092-360)
  • Outer sheath colour: Red

Application/ Use:

  • Fixed installation for medum voltage (MV) power in both EX- and safe areas, general purposes.
  • For installation in areas exposed to MUD and drilling / cleaning fluids.
  • Meets the MUD resistance requirement in NEK TS 606:2009

RFOU 12 2024kV P19 P21

RFOU 18/30 (36) kV P20/ P22

  • Power Cable Fixed Installation.
  • Conductor: Tinned stranded and compressed copper (STCC), IEC 60228 Class2
  • Conductor screen semiconductive: Semiconductive layer (EP-rubber)
  • Insulation: (R) EP-rubber, IEC 60092-360 (EPR)
  • Insulation screen semiconductive: Semiconductive layer (EP-rubber)
  • Lay up / Shielding: Cores are laid up together. Cores are identified by Brown, Black or Grey threads under and over the metallic screen on each conductor.
  • Inner covering: (F) Flame retardant and halogen-free thermoset compound
  • Tape over inner covering: PET-tape
  • Armour / screen: (O) Tinned annealed copper wire braid
  • Tape over armour: PET-tape
  • Outer sheath: (U) Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-360)
  • Outer sheath colour: Red

Application/ Use:

  • Fixed installation for medium voltage (MV) power in both EX- and safe areas, general purposes.
  • For installation in areas exposed to MUD and drilling / cleaning fluids.

RFOU MV 3x WEB

RFOU-HCF 6/10 (12) kV P30/ 1100°C / 30-60 minutes

  • Power Cable Fixed Installation.
  • Conductor: Tinned stranded and compressed copper (STCC), IEC 60228 Class2
  • Conductor screen semiconductive: Semiconductive layer (EP-rubber)
  • Insulation: (R) EP-rubber, IEC 60092-360 (EPR)
  • Insulation screen semiconductive: Semiconductive alyer (EP-rubber)
  • Lay up / Shielding: Cores are laid up together. Cores are identified by Brown, Black or Grey threads under and over the metallic screen on each conductor.
  • Inner covering: (F) Flame retardant and halogen-free thermoset compound
  • Tape over inner covering: PET-taper
  • Armour / screen: (O) Tinned copper wire braid
  • Tape over armour / screen: PET-tape
  • Outer sheath: (U) Flame retardant, halogen-free and mud resistant thermoset, SHF2 (IEC 60092-360)
  • HCF protection: -HCF Extruded heatblock compound
  • Tape: Lapped glassfibre tape
  • Overall sheath: Flame retardant, halogen-free thermoplastic compound, SHF1 (IEC 60092-360)
  • Outer sheath colour: Red

Application/ Use:

  • Fixed installation for medium voltage (MV) power in both EX- and safe areas, emergency and critical systems where requirement for fire resistance is vital.

RFOU HCF 6 1012kV P30 Hydrocarbon Fire

RFOU-HCF 8,7/15 (17,5) kV P31 / 1100°C / 30-60 minutes

  • Power Cable Fixed Installation.
  • Conductor: Tinned stranded and compressed copper (STCC), IEC 60228 Class2
  • Conductor screen semiconductive: Semiconductive layer (EP-rubber)
  • Insulation: (R) EP-rubber, IEC 60092-360 (EPR)
  • Insulation screen semiconductive: Semiconductive layer (EP-rubber)
  • Lay up / Shielding: Cores are laid up together. Cores are identified by Brown, Black or Grey threads under and over the metallic screen on each conductor.
  • Inner covering: (F) Flame retardant and halogen-free thermoset compound
  • Tape over inner covering: PET tape
  • Armour / screen:  (O) Tinned copper wire braid
  • Tape over armour / screen: PET tape
  • Outer sheath: (U) Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-360)
  • HFC protection: -HFC Extruded heatblock compound
  • Tape: Lapped glassfibre tape
  • Overall sheath: Flame retardant, halogen-free thermoplastic compoun, SHF1 (IEC 60092-360)
  • Outer sheath colour: Red

Application/ Use:

  • Fixed installation for medium voltage (MV) power in both EX- and safe areas, emergency and critical systems where requirement for fire resistance is vital.

RFOU HCF 8.7 1517.5kV P31 Hydrocarbon Fire

RFOU-HCF 18/30 (36) kV P33 / 1100°C / 30-60 minutes

  • Power Cable Fixed Installation.
  • Conductor: Tinned stranded and compressed copper (STCC), IEC 60228 Class2
  • Conductor screen semiconductive: Semiconductive layer (EP-rubber)
  • Insulatione: (R) EP-rubber, IEC 60092-360 (EPR)
  • Insulation screen semiconductive: Semiconductive layer (EP-rubber)
  • Lay up / Shielding: Cores are laid up together. Cores are identified by Brown, Black or Grey threads under and over the metallic screen on each conductor.
  • Inner covering: (F) Flame retardant and halogen-free thermoset compound
  • Tape over inner covering: PET tape
  • Armour / screen: (O) Tinned copper wire braid
  • Tape over armour / screen: PET tape
  • Outer sheath: (U) Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-360)
  • HFC protection: -HFC Extruded heatblock compound
  • Tape: Lapped glassfibre tape
  • Overall sheath: Flame retardant, halogen-free thermoplastic compound, SHF1 (IEC 60092-360)
  • Outer sheath colour: Red

Application/ Use:

  • Fixed installation for medum voltage (MV) power in both  EX- and safe areas, emergency and critical systems where requirement for fire resistance is vital.

RFOU HCF 18 3036kV P33 Hydrocarbon Fire


Reservation:

But be aware - this site - ex-products.eu, and its owner / webmaster can not be held responsible for any faults, information or any thinkable according to this lists.

It is the user's responsibility to ascertain if a particular product is safe and without risk to health and safety by virtue of its location in a hazardous area, i.e. classification of zones, gas groups, ignition temperatures, etc. Both the specifier and user should be thoroughly familiar with standard mentioned on this sites or any document within.

Whilst every care has been taken in the compilation of this document, we regrets that it cannot accept responsibility for any errors or omissions contained herein. Readers should not rely upon the information contained in this document or site without seeking specific safety advice and ensuring that their own particular circumstances are in accordance with the matters set out.

Utvalgte artikler

Husk at også innbruddstyver sjekker Facebook.

5 spørsmål og svar/råd.

Hva bør du gjøre når du skal reise bort?

Les mer …

Noen søketips.

Standardsøk, Katalogsøk.

Vi vil i denne oversikten, etterhvert som vi blir kjent med det, legge inn opplysninger som kan gjøre det litt lettere å søke etter linker, leverandører osv.. 

Les mer …

Utvalgte linker

  • GotogateGotogateSidevisning: 997Besøk: 150Opprettet:
  • Inkclub ABInkclub ABSidevisning: 575Besøk: 114Opprettet:
  • RogalandsguidenRogalandsguidenSidevisning: 1,546Besøk: 236Opprettet:
  • LensOn ABLensOn ABSidevisning: 553Besøk: 115Opprettet:
  • PRO ISP ASPRO ISP ASSidevisning: 1,000Besøk: 123Opprettet:
  • Booking.comBooking.comSidevisning: 1,356Besøk: 136Opprettet:

Nyeste linker

Populære linker

Infoklikk.no

Hjelper deg med å finne ressurser.

Dagens dato:

Infoklikk.no kan ikke på noen måte gjøres ansvarlig for innholdet på eksterne nettsteder som er linket på eller til Infoklikk.no sine sider. / Infoklikk.no - can not be held responsible for any content on any external website linked on or to the Infoklikk.no website.