Instrumentation Cables - BU /BFOU - Collective Screen
|
BU(c) 150/250 (300)V S14 Unarmoured
- Instrumentation Cable
- Conductor: Tinned annealed stranded circular copper (STCC), IEC 60228 Class2
- Insulation: (B) Mica-tape + EP-rubber, IEC 60092-360 (EPR)
- Pair / Triple / Quad twisting: Color coded cores twisted together and wrapped with polyester tape. Pairs / Triples are laid up collectively and screened by copper backed polyester tape with tinned copper drain wire. Pairs / triples are identified by numbered tape or by numbers printed directly on the insulated conductors.
- Inner covering: No inner covering. (Additional tapes may be applied)
- Armour / screen: Nor armour.
- Outer sheath: (U) Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-360)
- Outer sheath colour: Grey or Blue
|
Application/ Use:
- Fixed installation for instrumentation, communication, Control and alarm systems in both EX- (Zone 2) and safe areas, emergency and critical systems where requirement for fire resistance exists.
- Meets the mud resistant requirements in NEK TS 606:2009.
|
BFOU(c) 150/250 (300)V S4/S8
- Instrumentation Cable
- Conductor: Tinned annealed stranded circualr copper (STCC), IEC 60228 Class2
- Insulation: (B) Mica-tape + EP-rubber, IEC 60092-360 (EPR)
- Pair / Triple / Quad twisting: Color coded cores twisted together and wrapped with polyester tape. Pairs / Triples are laid collectively and screened by copper backed polyester tape with tinned copper drain wire. Pairs / triples are identified by numbered tape or by numbers printed directly on the insulated conductors.
- Inner covering: (F) Flame retardant and halogen-free thermoplastic compound
- Tape over inner covering: PET-tape
- Armour / screen: (O) Tinned annealed copper wire braid
- Tape over armour / screen: PET tape
- Outer sheath: (U) Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-360)
- Outer sheath colour: Grey or Blue
|
Application/ Use:
- Fixed installation for instrumentation, communication, Control and alarm systems in both EX-(Zone 0, 1 & 2) and safe areas, emergency and critical systems whre requirement for fire resistance exists.
- Meets the mud resistant requirements in NEK TS 606:2009
|
BFOU(c) 150/250 (300)V S4/S8 Arctic Grade
- Instrumentation Cable
- Conductor: Tinned annealed stranded circular copper (STCC), IEC 60228 Class2
- Insulation: (B) Mica-tape + EP-rubber, IEC 60092-351 (EPR)
- Pair / Triple / Quad twisting: Color coded cores twisted together and wrapped with polyester tape. Pairs / Triples are laid up collectively and screened by copper backed polyester tape with tinned copper drain wire. Pairs / triples are identified by numbered tape or by numbers printed directly on the insulated conductors.
- Inner covering: (F) Flame retardant and halogen-free thermoplastic compound
- Tape over inner covering: PET-tape
- Armour / screen: (O) Tinned annealed copper wire braid
- Tape over armour / screen: PET-tape
- Outer sheath: (U) Flame retardant, halogen-free, mud and cold bend / cold impact resistant thermoset compound, SHF2 (IEC 60092-359)
- Outer sheath colour: Grey or Blue
|
Application/ Use:
- Fixed installation for instrumentation, communication, Control and alarm systems in both EX- and safe areas, emergency and critical systems where requirement for fire resistance exists.
- Meet the OIL & MUD resistance requirement in NEK TS 606:2009.
- Meets the cold bend / cold impact requirement in CSA 22.2 0.3-01 and IEC 60092-350 Clause 8.9 & Annex E at -40°C / -35°C.
|
BFOU-HCF(c) 250V S16 / 1100°C / 30 minutes
- Instrumentation Cable
- Conductor: Tinned stranded circular copper, IEC 60228 Class2
- Insulation: (B) Mica-tape + EP-rubber, IEC 60092-360 (EPR)
- Pair / Triple / Quad twisting: Color coded cores twisted together and wrapped with polyester tape. Pairs / Triples are laid up collectively and screened by copper backed polyester tape with tinned copper drain wire. Pairs / triples are identified by numbered tape or by numbers printed directly on the insulated conductors.
- Inner covering: (F) Flame retardant and halogen-free thermoplastic compound
- Tape over inner covering: PET tape
- Armour / screen: (O) Tinned copper wire braid
- Tape over armour / screen: PET tape
- Outer sheath: (U) Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-360)
- HFC protection: -HFC Extruded heatblock compound
- Tape: Lapped glassfibre tape
- Overall sheath: Flame retardant, halogen-free thermoplastic compound, SHF1 (IEC 60092-360)
- Outer sheath colour: Grey, Blue or Black
|
Application/ Use:
- Fixed installation for instrumentation, communication, Control and alarm systems in both EX- and safe areas, emergency and critical systems where requirement for hydrocarbon fire resistance is vital.
|
BFOU-XFR(c) 150/250 (300)V / Mud resistant
- Instrumentation Cable
- Conductor: Tinned annealed stranded circular copper (STCC), IEC 60228 Class2
- Insulation: Mica-tape + EP-rubber, IEC 60092-360 (EPR)
- Pair / Triple / Quad twisting: Color coded cores twisted together and wrapped with polyester tape. Pairs / Triples are laid up collectively and screened by copper backed polyester tape with tinned copper drain wire. Pairs / triples are identified by numbered tape or by numbers printed directly on the insulated conductors.
- Inner covering: (F) Flame retardant and halogen-free thermoplastic compound
- Tape over inner covering: PET tape
- Armour / screen: (O) Tinned annealed copper wire braid
- Tape over armour / screen: PET tape
- Outer sheath: (U) Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-360)
- Outer sheath colour: Grey or Blue
|
Application/ Use:
- Fixed installation for instrumentation, communication, Control and alarm systems in both EX- and safe areas, emergency and critical systems where requirement for fire resistance exists.
- Meets the mud resistant requirements in NEK TS 606:2009.
- Cables have extended fire resistant (XFR) properties to IEC 60331-1&2 including water spray according to EN 50200 Annex E (90 minutes).
|
Instrumentation Cables - BU /BFOU - Induvidual Screen
|
BU(i) 150/250 (300)V S13 Unarmoured
- Instrumentation Cable
- Conductor: Tinned annealed stranded circular copper (STCC), IEC 60228 Class2
- Insulation: (B) Mica-tape + EP-rubber, IEC 60092-360 (EPR)
- Pair / Triple / Quad twisting: Color coded cores twisted together. Pairs / Triples are screened by copper backed polyester tape with tinned copper drain wire. Each pair / triple is wrapped with polyester tape to prevent electrical contact with adjacent pairs / triples. Pairs / triples are identified by numbers printed directly on the insulated conductors.
- Lay up / Shielding: Individually shielded pairs / triples / quads are laid up in concentric layers and wrapped with a PETP tape.
- Inner covering: No inner covering. (Additional tapes may be applied)
- Armour / screen: No armour.
- Outer sheath: (U) Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-360)
- Outer sheath colour: Grey or Blue
|
Application/ Use:
- Fixed installation for instrumentation, communication, control and alarm systems in both EX- (Zone 2) and safe areas, emergency and critical systems where requirement for fire resistance exists.
- Meets the mud resistant requirements in NEK TS 606:2009.
|
BFOU(i) 150/250 (300)V S3/S7
- Instrumentation Cable
- Conductor: Tinned annealed stranded circular copper (STCC), IEC 60228 Class2
- Insulation: (B) Mica-tape + EP-rubber, IEC 60092-360 (EPR)
- Pair / Triple / Quad twisting: Color coded cores twisted together. Pairs / Triples are screened by copper backed polyester tape with tinned copper drain wire. Each pair / triple is wrapped with polyester tape to prevent electrical contact with adjacent pairs / triples. Pairs / triples are identified by numbered tape or by numbers printed directly on the insulated conductors.
- Lay up / Shielding: Individually shielded pairs / triples / quads are laid up in concentric layers and wrapped with PETP tape.
- Inner covering: (F) Flame retardant and halogen-free thermoplastic compound
- Tape over inner covering: PET tape
- Armour / screen: (O) Tinned annealed copper wire braid
- Tape over armour / screen: PET tape
- Outer sheath: (U) Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-360)
- Outer sheath colour: Grey or Blue
|
Application/ Use:
- Fixed installation for instrumentation, communication, Control and alarm systems in both EX- (Zone 0, 1 & 2) and safe areas, emergency and critical systems where requirement for fire resistance exists.
- Meets the mud resistant requirements in NEK TS 606:2009.
|
BFOU(i) 150/250V (300)V S3/S7 Arctic Grade
- Instrumentation Cable
- Conductor: Tinned annealed stranded circular copper (STCC), IEC 60228 Class2
- Insulation: (B) Mica-tape + EP-rubber, IEC 60092-351 (EPR)
- Pair / Triple / Quad twisting: Color coded cores twisted together. Pairs / Triples are screened by copper backed polyester tape with tinned copper drain wire. Each pair / triple is wrapped with polyester tape to prevent electrical contact with adjacent pairs / triples. Pairs / triples are identified by numbered tape or by numbers printed directly on the insulated conductors.
- Lay up / Shielding: Individually shielded pairs / triples / quads are laid up in concentric layers and wrapped with a PETP tape.
- Inner covering: (F) Flame retardant and halogen-free thermoplastic compound
- Tape over inner covering: PET tape
- Armour / screen: (O) Tinned annealed copper wire braid
- Tape over armour / screen: PET tape
- Outer sheath: (U) Flame retardant, halogen-free, mud and cold bend / cold impact resistant thermoset compound, SHF2 (IEC 60092-359)
- Outer sheath colour: Grey or Blue
|
Application/ Use:
- Fixed installation for instrumentation, communication, Control and alarm systems in both EX- and safe areas, emergency and critical systems where requirement for fire resistance exists.
- Meets the OIL & MUD resistance requirement in NEK TS 606:2009.
- Meets the cold bend / cold impact requirement in CSA 22.2 0.3-01 and IEC 60092-350 Clause 8.9 & Annex E at -40°C / -35°C.
|
BFOU-HCF(i) 250V S15 / 1100°C / 30 minutes
- Instrumentation Cable
- Conductor: Tinned stranded circular copper, IEC 60228 Class2
- Insulation: (B) Mica-tape + EP-rubber, IEC 60092-360 (EPR)
- Pair / Triple / Quad twisting: Color coded cores twisted together. Pairs / Triples are screened by copper backed polyester tape with tinned copper drain wire. Each pair / triples is wrapped with polyester tape to prevent electrical contact with adjacent pairs / triples. Pairs / triples are identified by numbered tape or by numbers printed directly on the insulated conductors.
- Inner covering: (F) Flame retardant and halogen-free thermoplastic compound
- Tape over inner covering: PET tape
- Armour / screen: (O) Tinned copper wire braid
- Tape over armour / screen: PET tape
- Outer sheath: (U) Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-360)
- HFC protection: -HFC Extruded heatblock compound
- Tape: Lapped glassfibre tape
- Overall sheath: Flame retardant, halogen-free thermoplastic compound, SHF1 (IEC 60092-360)
- Outer sheath colour: Grey, Blue or Black
|
Application/ Use:
- Fixed installation for instrumentation, communication, Control and alarm systems in both EX- and safe areas, emergency and critical systems where requirement for hydrocarbon fire resistance is vital.
|
BFOU-XFR(i) 150/250 (300)V / Mud resistant
- Instrumentation Cable
- Conductor: Tinned annealed stranded circular copper (STCC), IEC 60228 Class2
- Insulation: (B) Mica-tape + EP-rubber, IEC 60092-360 (EPR)
- Pair / Triple / Quad twisting: Color coded cores twisted together. Pairs / Triples are screened by copper backed polyester tape with tinned copper drain wire. Each pair / triples is wrapped with polyester tape to prevent electrical contact with adjacent pairs / triples. Pairs / triples are identified by numbered tape or by numbers printed directly on the insulated conductors.
- Lay up / Shielding: Individually shielded pairs / triples / quads are laid up in concentric layers and wrapped with a PETP tape.
- Inner covering: (F) Flame retardant and halogen-free thermoplastic compound
- Tape over inner covering: PET tape
- Armour / screen: (O) Tinned annealed copper wire braid
- Tape over armour / screen: PET tape
- Outer sheath: (U) Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-360)
- Outer sheath colour: Grey or Blue
|
Application/ Use:
- Fixed installation for instrumentation, communication, Control and alarm systems in both EX- and safe areas, emergency and critical systems where requirement for fire resistance exists.
- Meets the mud resistant requirements in NEK TS 606:2009.
- Cables have extended fire resistant (XFR) properties to IEC 60331-1&2 including water spray according to EN 50200 Annex E (90 minutes).
|